Heating, Ventilating, Cooling, Mechanical Contractors Industry Terminology

ACCA (Air Conditioning Contractors of America)

A U.S. trade association that develops HVAC design, installation, and maintenance standards (e.g., Manuals J, S, D) and offers contractor accreditation and training.

Per ACCA Manual J, the sensible load comes to 48,000 BTU/hr.; We follow ACCA Quality Installation guidelines on all residential jobs.; Let’s cite ACCA Manual D for the duct sizing submittal.


Absorption Chiller

A chiller that uses heat (steam, hot water, or direct-fired gas) instead of electricity-driven compressors to drive a refrigeration cycle, typically with lithium bromide–water. Ideal where waste heat is available.

A steam-driven absorption chiller will capture waste heat from the CHP.; Absorption works for our hospital because electric demand charges are high.; We’ll compare LiBr absorption vs. electric centrifugal in the LCCA.


ACH (Air Changes per Hour)

A ventilation metric indicating how many times the air within a space is replaced in one hour; calculated from airflow and room volume.

Labs typically require 6–12 ACH by code and risk assessment.; Our energy model shows we can reduce ACH at night with setbacks.; To meet 62.1, the classroom needs 4 ACH of outdoor air.


AHU (Air Handling Unit)

A central unit that conditions and circulates air, typically containing coils, filters, fans, dampers, and controls; can be constant-volume or VAV.

The new AHU-3 has an energy recovery wheel and MERV 13 filters.; We’ll stage the coil replacement during the AHU outage window.; Trend logs show AHU static pressure can be reset to save energy.


Air-Cooled Condenser

A heat-rejection device that transfers condenser heat to outdoor air via fans and finned coils, eliminating cooling towers and water usage.

We chose air-cooled condensers to avoid water treatment.; Noise screening is needed for the roof air-cooled banks.; At 95°F ambient, the air-cooled condenser limits chiller capacity.


ASHRAE

A global professional society that publishes HVAC&R standards and guidelines (e.g., 62.1 ventilation, 90.1 energy, 55 thermal comfort) and industry handbooks.

Ventilation rates are per ASHRAE 62.1.; Our baseline energy model follows ASHRAE 90.1 Appendix G.; The setpoints align with ASHRAE 55 comfort criteria.


BAS (Building Automation System)

A control platform that monitors and optimizes building systems (HVAC, lighting, etc.) using sensors, controllers, and communication protocols like BACnet.

Let’s add a BAS alarm for high chilled-water delta-T.; The BAS trend shows the VAVs are hunting the setpoint.; We’ll integrate the boilers via BACnet to the BAS.


BIM (Building Information Modeling)

A digital 3D information model used for design, coordination, fabrication, and facility management; enables clash detection and quantity takeoffs.

Run a Navisworks clash between duct and the steel.; We’ll export spool drawings directly from the BIM model.; The owner requested COBie data for FM from BIM.


BTU (British Thermal Unit)

A unit of heat energy; roughly the energy to raise 1 lb of water by 1°F. In HVAC, capacity is often in BTU/hr; 12,000 BTU/hr equals 1 refrigeration ton.

This split system is rated at 36,000 BTU/hr.; The load calc adds 10,000 BTU/hr for lighting.; We’ll convert BTU/hr to kW for the energy model.


Building Envelope

The physical boundary between conditioned and unconditioned spaces (walls, roof, windows, doors) that drives heat gain/loss, air leakage, and moisture control.

Upgrading the envelope cuts the HVAC tonnage.; Infiltration through the envelope is spiking heating loads.; Specify U-values and SHGCs that meet code for the envelope.


CAPEX (Capital Expenditure)

Upfront investment for assets such as HVAC equipment and infrastructure, distinct from OPEX; considered in budgeting and life-cycle analysis.

VRF lowers CAPEX versus a central plant on this project.; We’ll balance CAPEX and OPEX using NPV.; The owner approved CAPEX for two new chillers.


Change Order

A formal modification to contract scope, cost, or schedule, typically initiated by owner or GC and documented with pricing and impact.

Rerouting the duct riser will require a change order.; Submit CO pricing for the added FCUs and controls.; The CO extends substantial completion by 10 days.


Chiller

Central cooling equipment that removes heat from water (or glycol) using vapor-compression or absorption cycles; types include centrifugal, screw, scroll.

We’ll add a 500-ton centrifugal chiller to the plant.; Low delta-T is reducing chiller efficiency.; Specify VSD chillers with N+1 redundancy.


Commissioning (Cx)

A quality process to verify systems are designed, installed, and performing to the owner’s requirements through testing, documentation, and training; RCx applies to existing buildings.

Cx functional tests begin next week.; The Cx agent requested more BAS trend data.; RCx saved 18% by fixing control sequences.


Compressor

The component that raises refrigerant pressure and temperature in a vapor-compression cycle; common types are scroll, screw, and centrifugal.

The screw compressor is short-cycling.; We’ll stage compressors based on load and kW/ton.; VFDs on compressors improve part-load efficiency.


Condenser

A heat exchanger where refrigerant rejects heat and condenses from vapor to liquid; can be air-cooled or water-cooled.

Clean the condenser coils to restore capacity.; Tower setpoint affects the condenser approach.; Ambient temp limits air-cooled condenser performance.


COP (Coefficient of Performance)

Efficiency ratio of heating or cooling output (kW) to input power (kW); higher is better. Comparable to EER/SEER for cooling but dimensionless.

This heat pump has a COP of 3.5 at 47°F.; Raising chilled water temp increases chiller COP.; We’ll compare COP curves at part load.


DDC (Direct Digital Control)

Microprocessor-based control of HVAC using sensors, actuators, and software; replaces pneumatic systems and enables advanced sequences and trending.

Upgrade the AHU to DDC with BACnet MSTP.; DDC alarms will alert us to high static pressure.; Tune the DDC loops to stop valve hunting.


Design-Build

A project delivery method in which design and construction are under a single contract, enabling faster decisions, collaboration, and cost control.

Design-build lets us fast-track equipment procurement.; We’re proposing a design-build GMP with shared savings.; Design-build reduces coordination RFIs.


Duct Static Pressure

The air pressure within a duct system, commonly controlled at a setpoint and reset based on VAV demand to reduce fan energy and noise.

Lower the static setpoint to 1.2 in. w.c. during low load.; We’ll add a duct static sensor downstream of the AHU.; Static pressure reset saved 20% fan energy.


Economizer

A control strategy or section that uses outdoor air for free cooling when conditions are favorable (dry-bulb or enthalpy-based).

Enable the economizer below 55°F and low enthalpy.; Faulty dampers are defeating the economizer cycle.; Title 24 requires integrated economizers on these RTUs.


ERV (Energy Recovery Ventilator)

A device that exchanges heat and moisture between incoming outdoor air and exhaust air to reduce heating/cooling loads and maintain humidity.

Add an ERV to precondition the OA for the AHU.; The enthalpy wheel boosts winter humidity.; ERV effectiveness improves our energy model.


Fan Coil Unit (FCU)

A terminal unit with a fan and heat exchanger (2-pipe or 4-pipe) that conditions local spaces; common in hotels and apartments.

The guestrooms use 4-pipe FCUs with DOAS ventilation.; Replace the FCU motors with ECMs.; Balance the FCUs after coil cleaning.


GMP (Guaranteed Maximum Price)

A contract type where the contractor is paid actual costs up to a ceiling price; savings may be shared, overruns beyond GMP are the contractor’s risk.

We’ll carry a 5% MEP contingency in the GMP.; Owner accepted a GMP with allowances for controls.; Shared savings incentivize VE under the GMP.


GWP (Global Warming Potential)

A measure of how much heat a greenhouse gas traps versus CO₂ over a time horizon; drives refrigerant selection and regulatory compliance.

We’re phasing out R-410A due to high GWP.; Consider R-454B for lower GWP in new RTUs.; Specs cap refrigerant GWP per local regs.


Heat Exchanger

A device that transfers heat between fluids without mixing; types include plate-and-frame, shell-and-tube, and coaxial.

Add a plate-and-frame HX for waterside economizer.; We’ll isolate glycol with a heat exchanger at the tower.; HX fouling raised approach temperatures.


Heating and Cooling Load Calculation

The analytical process to determine required HVAC capacity based on envelope, internal gains, ventilation, and climate (e.g., ACCA Manual J/S or ASHRAE methods).

The load calc shows 150 tons at peak.; We updated loads after the glazing change.; Diversified load profiles drive chiller sizing.


HVAC

Heating, ventilation, and air conditioning—the set of mechanical systems that condition and distribute air and fluids to maintain comfort and indoor air quality.

Our firm self-performs HVAC and plumbing.; The HVAC scope includes controls and TAB.; HVAC accounts for 40% of building energy.


IAQ (Indoor Air Quality)

The condition of air inside buildings as it relates to occupants’ health and comfort; influenced by ventilation, filtration, humidity, particulates, VOCs, and CO₂.

We’re targeting better IAQ with MERV 13 filters.; CO₂ sensors will modulate ventilation for IAQ.; IAQ testing is part of the turnover package.


IFC Drawings (Issued for Construction)

The final construction drawing set released for building; used for permitting, fabrication, installation, and as-built markups.

We can’t fabricate until the IFC set drops.; Coordinate spools against the IFC ceiling heights.; Redline the IFC drawings during field changes.


Lean Construction

A delivery philosophy focused on maximizing value and minimizing waste via tools like Last Planner, pull planning, takt time, and prefabrication.

Set up a pull plan for the mechanical floor.; We’re using takt zones for duct install.; Lean prefabrication cut field labor by 25%.


Lockout/Tagout (LOTO)

A safety procedure to de-energize and prevent the startup of equipment during service; required by OSHA to protect workers.

Perform LOTO before opening the RTU panel.; LOTO points are listed in the JHA.; The crew completed LOTO training last month.


MAU (Make-Up Air Unit)

An air handler that provides 100% outdoor air to replace exhaust (e.g., kitchens, labs), often with heating and cooling to temper incoming air.

The kitchen hood requires a dedicated MAU.; Heat the MAU with indirect gas fired sections.; Balance the MAU to match exhaust flow.


MEP (Mechanical, Electrical, Plumbing)

The coordinated building systems disciplines; MEP contractors and engineers plan, install, and commission integrated infrastructure.

The MEP coordination meeting is at 10 a.m.; MEP rough-in must finish before drywall.; We’re the MEP prime on this design-build.


MERV (Minimum Efficiency Reporting Value)

A filtration rating (1–16) describing a filter’s ability to capture particles; higher MERV captures smaller particles but increases pressure drop.

Specs call for MERV 13 pre-occupancy.; Check fan static for the MERV upgrade.; We’ll stage MERV 8 prefilters and MERV 13 finals.


NPV (Net Present Value)

A life-cycle financial metric that discounts future cash flows to present value to evaluate investments across CAPEX and OPEX.

Variable-speed pumps win on NPV over 15 years.; We used a 6% discount rate in the NPV.; High-efficiency chillers have a positive NPV.


O&M (Operations and Maintenance)

Activities, manuals, and procedures to operate and maintain systems for reliability and efficiency; includes PM schedules and training.

Deliver O&M manuals at substantial completion.; Add quarterly PM to the O&M plan for the boilers.; O&M staff want hands-on BAS training.


PID Control

A feedback control algorithm (Proportional–Integral–Derivative) that modulates outputs (valves, dampers, VFDs) to maintain setpoints with minimal overshoot.

Retune the PID loop for discharge air temp.; Poor PID tuning is causing oscillation.; We’ll switch to PI only on this slow loop.


Prefabrication

Off-site fabrication of assemblies (duct sections, pipe racks, equipment skids) to improve safety, quality, schedule, and cost.

We’ll prefab the pump skid with VFDs and piping.; Ductwork is being prefabricated by zone.; Prefab cut our installed cost by 18%.


Psychrometrics

The study of moist air properties and processes (temperature, humidity, enthalpy) used to design coils, dehumidification, and economizers.

Plot the mixed-air state on the psych chart.; We need reheat to hit the psychrometric target.; Enthalpy control uses psychrometric comparisons.


QA/QC (Quality Assurance/Quality Control)

Systems and inspections to ensure work meets standards and specifications, including ITPs, checklists, testing, and documentation.

TAB is part of our QA/QC plan.; QC rejected the weld due to lack of penetration.; Update the QA/QC checklist for coil installation.


RFI (Request for Information)

A formal question to clarify design intent, scope, or conflicts; responses can affect cost and schedule.

Submit an RFI on the conflicting duct elevations.; The RFI response approved an alternate VAV box.; Track RFIs and impacts in the log.


Refrigerant

The working fluid in a vapor-compression cycle; selection considers capacity, efficiency, GWP, toxicity, and flammability class (A1, A2L, etc.).

Charge the system with R-454B per spec.; Local code now allows A2L refrigerants.; We’ll recover and weigh out the old refrigerant.


Retrofit/Retro-Commissioning (RCx)

Upgrading existing systems or re-optimizing controls to restore or improve performance, comfort, and energy efficiency.

RCx revealed failed OA dampers.; LED and VFD retrofits qualified for rebates.; We’ll retrofit coils and add DDC to the AHUs.


Rooftop Unit (RTU)

A packaged HVAC unit installed on a roof that provides heating and cooling (often gas heat and DX cooling), commonly serving zones directly.

Replace RTU-5 with a 20-ton high-efficiency model.; The curb adapter will fit the new RTU footprint.; Add an economizer section to each RTU.


TAB (Testing, Adjusting, and Balancing)

Field procedures to verify and tune air and water flows to design values, documented in certified reports.

Schedule TAB after controls are commissioned.; Final TAB shows all VAVs within 10%.; Hydronic TAB corrected low delta-T issues.


Value Engineering (VE)

A structured process to improve value by reducing cost or improving performance without compromising required function or quality.

VE: swap to ECM fan arrays to save energy.; We proposed VE to downsize pumps after recalcs.; VE workshop identified four acceptable alternates.


VAV (Variable Air Volume)

An air distribution strategy where airflow to zones modulates to meet load while supply air temperature is held roughly constant.

Reset duct static based on VAV damper positions.; The VAV boxes need new reheat valves.; Convert CAV to VAV for energy savings.


VFD (Variable Frequency Drive)

An electronic device that varies motor speed to match load, reducing energy and wear on fans, pumps, and compressors.

Add VFDs to the CHW pumps for delta-P control.; The VFD tripped on overcurrent—check filters.; VFD turndown improves part-load efficiency.


VRF/VRV (Variable Refrigerant Flow)

A multi-zone HVAC system in which outdoor units vary refrigerant flow to multiple indoor units; can provide simultaneous heating and cooling with heat recovery.

VRF was selected for the office fit-out.; Mind the line length limits in the VRF design.; Heat-recovery VRF reduces reheat energy.


Was this page helpful? We'd love your feedback — please email us at feedback@dealstream.com.