Masonry Contractors Industry Terminology

Air Barrier

A continuous system of materials designed to control air leakage through the building envelope, improving energy performance and moisture management. Typically fluid-applied or self-adhered sheet membranes, tested to ASTM E2357/E2178.

“Ensure the air barrier is continuous behind the brick veneer with sealed laps and transitions.” “Seal all anchor-penetrations to the air barrier per TMS 602.” “Coordinate air barrier with WRB and vapor retarder to avoid double barriers.”


Anchor Tie (Masonry Tie)

Metal connectors that secure a masonry veneer wythe to a backup wall (CMU, concrete, or studs) to transfer lateral loads while allowing differential movement. Includes corrugated, wire, perforated plate, thermal clips, and seismic anchors; spacing and embedment per TMS 402/602.

“Use adjustable stainless-steel veneer anchors at 16 in O.C. each way per design.” “Terminate joint reinforcement and use slip ties across control joints.” “Replace corroded mild-steel ties with Type 304 stainless near the coast.”


ASTM

The American Society for Testing and Materials publishes consensus standards referenced in masonry specifications for units, mortar, grout, ties, and testing methods.

“Specify facing brick to ASTM C216, Type FBS.” “CMU shall comply with ASTM C90, medium weight.” “Mortar shall meet ASTM C270, and grout ASTM C476.”


Bed Joint

The horizontal mortar joint between masonry courses. Thickness and workmanship affect alignment, bond, and water resistance.

“Maintain uniform 3/8-inch bed joints for brick modular layout.” “Use face-shell bedding for CMU unless full-bed is specified at bearing.” “Keep exterior bed joints solid to improve water resistance.”


Bond Beam

A reinforced horizontal element within masonry (often formed with U-shaped units or knockouts) that restrains movement, distributes loads, and ties walls together. Filled with grout and reinforcing steel.

“Install a bond beam at the top course to tie the wall and distribute loads.” “Use U-blocks to form the bond beam and place continuous rebar.” “Coordinate bond beam lap splices and grout consolidation.”


Brick Veneer

A non-loadbearing exterior wythe of clay brick tied to a structural backup that provides the building’s lateral and vertical support. Designed to drain and accommodate movement.

“Provide brick veneer over steel-stud backup with adjustable anchors.” “Install through-wall flashing and weeps at the base of the brick veneer.” “Include expansion joints at prescribed spacing in clay brick veneers.”


Cavity Wall

A wall system with two wythes separated by an air/drainage space, typically a brick veneer and a CMU or concrete backup. The cavity allows drainage and ventilation; flashing and weeps direct water out.

“Maintain a 2-inch clear cavity with mortar collection devices at shelf angles.” “Install rigid or mineral wool insulation in the cavity without blocking drainage.” “Keep the cavity clean; no mortar bridging across the air space.”


CMU (Concrete Masonry Unit)

Modular concrete blocks used for structural and non-structural walls. Classified by weight, configuration, and face finish; can be reinforced and grouted to increase strength.

“8x8x16 nominal CMU, ASTM C90, medium weight.” “Grout fully grouted cells at shear wall locations.” “Use split-face CMU for the exposed facade.”


Control Joint

A vertical, intentionally weakened plane in CMU or concrete masonry that accommodates shrinkage and thermal movement to limit cracking. Joints are unbonded and sealed.

“Place control joints at re-entrant corners and at regular spacing per design.” “Use backer rod and sealant; do not bond mortar across the joint.” “Install slip ties or break joint reinforcement at control joints.”


Damp-Proofing

A coating or treatment that resists moisture penetration (not liquid water under pressure). Used for below-grade walls where hydrostatic pressure is not present.

“Apply asphaltic dampproofing to the exterior face of below-grade CMU.” “Dampproofing is not a substitute for waterproofing under hydrostatic pressure.” “Terminate dampproofing at grade per detail.”


Dowel (Rebar Dowel)

Short reinforcing bars used to connect new masonry to existing work or foundations, transferring loads across joints. Installed cast-in or post-installed with adhesives.

“Set #5 dowels at 32 inches O.C. to anchor CMU wall to footing.” “Use epoxy-set dowels for post-installed connections.” “Provide dowel caps where movement is required across joints.”


Efflorescence

A white, powdery salt deposit on masonry surfaces caused by water dissolving soluble salts and evaporating. Often cosmetic; indicates moisture movement.

“White staining appeared after heavy rains; likely efflorescence.” “Brush off efflorescence and address water entry; avoid immediate acid washing.” “Specify low-alkali materials and IWR to mitigate efflorescence.”


Expansion Joint

A vertical joint in masonry veneer (especially clay brick) designed to accommodate moisture-related and thermal expansion. The joint is sealed and not bonded.

“Provide expansion joints at prescribed spacing in clay brick veneer.” “Include an expansion joint where the veneer meets the concrete frame.” “Use color-matched sealant in expansion joints.”


Face Shell Bedding

A CMU laying method where mortar is applied only to the outer face shells, not the webs. Acceptable in many nonbearing conditions; full-bed is used where required.

“Place mortar on the face shells only unless full-bed is specified.” “Full-bed mortar required at bearing and under lintels.” “Ensure face-shell bedding does not reduce structural capacity where full bearing is needed.”


Fire-Resistance Rating (Masonry Assemblies)

The duration (in hours) a wall assembly resists fire exposure. Verified by tested assemblies or calculations; masonry often provides inherent fire resistance.

“Provide a 2-hour CMU fire wall per listed assembly.” “Solid grouting increases fire resistance for certain CMU walls.” “Use TMS 216 calculation or UL listings to document ratings.”


Flashing, Through-Wall

An impervious membrane installed within masonry walls to intercept and direct water to the exterior. Critical at bases, lintels, shelf angles, and parapets; requires end dams, laps, and weeps.

“Install through-wall flashing at shelf angles and over lintels with end dams.” “Lap flashing to the air barrier and provide weeps at 24 in O.C. (or per spec).” “Use stainless steel or EPDM where high durability is required.”


Grout

A fluid mixture of cementitious materials, sand, water (and sometimes pea gravel) used to fill CMU/brick cores and bond beams around reinforcement to create composite action.

“Use coarse grout for cells larger than 2x2 inches; fine grout otherwise.” “Target slump in the 8–11 inch range for proper flow and consolidation.” “Consolidate grout with rodding/vibration per TMS 602.”


Grout Lift and Pour Height

Code-limited vertical placement heights for grout to prevent segregation and ensure consolidation. Often placed in lifts and pours with cleanouts and reconsolidation.

“High-lift grouting requires cleanouts and staged placement.” “Limit lift heights and reconsolidate to avoid segregation.” “Follow TMS 402/602 for lift and pour limits.”


Head Joint

The vertical mortar joint between masonry units. Influences bond, alignment, and water resistance; tooling affects performance.

“Maintain 3/8-inch head joints for proper alignment.” “Tool head joints concave for exterior durability.” “Do not bridge movement joints with head-joint mortar.”


Hot-Weather Masonry

Construction practices and precautions used when high temperatures, sun, and wind increase evaporation and reduce workability and strength. Addresses unit conditioning, mortar handling, and curing.

“Pre-dampen high-absorption units and shade mortar boards.” “Shorten retempering time and protect fresh work from rapid drying.” “Follow TMS 602 hot-weather provisions when temps and wind are high.”


IBC (International Building Code)

Model building code that governs structural design, fire/life safety, and materials. References TMS 402/602 for masonry design and construction requirements.

“Design masonry per IBC-referenced TMS 402/602.” “Provide special inspections under IBC Chapter 17.” “Local jurisdiction adopted IBC 2024; verify amendments.”


Integral Water Repellent (IWR)

Admixtures added to CMU and/or mortar that reduce water absorption and capillary transport, improving moisture resistance of single-wythe and veneer systems.

“Use IWR CMU for single-wythe exterior walls.” “Mortar IWR must be compatible with unit IWR; follow manufacturer.” “IWR helps reduce efflorescence by limiting absorption.”


Joint Reinforcement

Prefabricated wire reinforcement placed in bed joints of masonry to control cracking, improve load distribution, and enhance structural performance.

“Provide ladder-type joint reinforcement every 16 inches vertically (per spec).” “Break reinforcement at control joints.” “Use stainless steel in severe exposure zones.”


Joint Tooling and Profiles

The shaping of mortar joints (concave, V, flush, raked, etc.) to affect weather resistance and appearance. Proper timing compacts mortar and reduces water intrusion.

“Specify concave tooling for exterior walls.” “Raked joints used for interior aesthetics; avoid on weather-exposed faces.” “Tool after initial set to compact and seal the joint face.”


LEED (Leadership in Energy and Environmental Design)

A voluntary green building rating system that awards points for energy, materials, water, and indoor environmental quality. Masonry can contribute via durability, recycled content, regional sourcing, and EPDs.

“Submit EPDs for brick and CMU to support LEED credits.” “Divert masonry waste to meet the project’s diversion goal.” “Light-colored pavers can contribute to heat island reduction.”


Lintel

A horizontal structural element spanning an opening in masonry to support loads above. Can be steel, reinforced masonry, or precast concrete.

“Provide galvanized steel angle lintels with end dams and flashing.” “Use reinforced CMU lintels for long spans.” “Confirm required bearing length at jambs.”


Masonry Cement vs Mortar Cement

Two binder types for mortar: masonry cement (blended cement/lime with additives, good workability) and mortar cement (engineered for higher bond and strength). Selection depends on performance requirements.

“Specify mortar cement Type S for higher bond in structural applications.” “Do not substitute masonry cement without approval.” “Verify compliance with ASTM C91 (masonry cement) vs C1329 (mortar cement).”


Mock-Up

A representative field-built sample panel or assembly used to confirm materials, details, workmanship, and aesthetics before production work proceeds.

“Build a full-height corner mock-up showing joints, flashing, and weeps.” “Use the mock-up for water-testing the veneer head detail.” “Approved mock-up becomes the quality benchmark.”


Mortar Types (Type M, S, N, O)

Mortars are classified by strength and application: Type M (highest), S, N, and O (lowest). Selection depends on structural and exposure requirements per ASTM C270.

“Type S for CMU shear walls and exterior veneers.” “Type N for standard brick veneer above grade.” “Type O for interior or historic repointing where lower strength is desired.”


NFPA 285

A fire test method evaluating vertical and lateral flame spread of wall assemblies containing combustible materials. Required by codes for many insulated veneer systems.

“Verify brick veneer with foam insulation passes NFPA 285.” “Submit assembly reports documenting compliance.” “Switch to mineral wool to simplify NFPA 285 requirements.”


Nominal vs Actual Dimensions

Nominal sizes include the standard joint thickness; actual sizes are the true manufactured dimensions. Layout and coursing rely on nominal modular dimensions.

“CMU nominal 8x8x16; actual 7-5/8 x 7-5/8 x 15-5/8.” “Use nominal dimensions for layout and coursing.” “Allow for 3/8-inch joints when coordinating openings.”


OSHA 1926 Subpart Q (Masonry Construction)

U.S. safety regulations specific to masonry construction addressing limited access zones, wall bracing, lifting, and other hazards.

“Establish a limited access zone during wall erection.” “Brace freestanding walls until the grout cures and design bracing is in place.” “Follow scaffold and hoisting rules in parallel with Subpart Q.”


Parapet

A low protective wall at a roof edge. Vulnerable to water entry and wind loading; requires robust flashing, copings, and movement detailing.

“Install through-wall flashing at the parapet base with weeps to the exterior.” “Cap with properly sloped copings and drip edges.” “Provide movement joints to accommodate thermal swings.”


Punch List

A list of outstanding deficiencies and incomplete items identified at the end of construction that must be corrected before final acceptance.

“Repoint chipped joints and clean efflorescence per punch list.” “Replace spalled brick at coordinates noted.” “Close all punch items before substantial completion.”


QA/QC

Quality assurance and quality control processes that govern planning, inspection, testing, and documentation to ensure the work meets specifications and code.

“Preinstallation meeting and mock-up approval are QA steps.” “Daily QC checks ensure joint thickness and tooling meet TMS 602.” “Log test reports for mortar and grout compressive strength.”


Rainscreen

A wall strategy that uses a drained/vented cavity behind cladding to manage water intrusion and promote drying. Requires a continuous air/WRB, flashing, and weeps.

“Use mortar nets to keep the rainscreen cavity clear.” “Vent the top of the cavity behind the veneer.” “Coordinate WRB/air barrier continuity in the rainscreen.”


RFI (Request for Information)

A formal question from contractor to design team seeking clarification of drawings/specs. Helps manage risk, schedule, and scope.

“RFI 023 clarifies shelf angle elevations at grid C.” “Submit an RFI to resolve conflicting details between A7.2 and S3.1.” “Track schedule impacts associated with late RFI responses.”


Reinforced Masonry

Masonry strengthened by steel reinforcement and grout to resist tension, shear, and bending, enabling structural walls, shear walls, and lintels.

“Provide #5 vertical bars at 24 inches O.C. in grouted cells.” “Bond beams at every third course tie the diaphragm to the wall.” “Lap splices and development lengths per TMS 402.”


Scaffold (Mast Climber/Frame)

Temporary elevated work platforms that provide access to wall faces. Includes frame, tube-and-coupler, and mast climbers; requires proper anchorage, loading, and safety controls.

“Use mast climbers for the 6-story brick facade.” “Inspect planks and tie-ins daily per OSHA.” “Do not overload platforms with pallets of brick beyond rated capacity.”


Shelf Angle

A steel angle anchored to the structure that supports brick veneer (often at floor levels), allowing differential movement between the frame and veneer.

“Install continuous galvanized shelf angle at each floor line.” “Provide thermal break pads behind the shelf angle.” “Flash over the shelf angle and provide weeps.”


Shop Drawings and Submittals

Contractor-prepared documents that detail fabrication, installation, and product selections for review and approval prior to construction.

“Submit shop drawings for shelf angles and anchors with calculations.” “Provide mortar and grout mix designs and EPDs.” “Maintain a submittal log to track approvals.”


Specified Masonry Compressive Strength (f'm)

The design compressive strength of the masonry assembly, established by unit strength tables or prism testing (ASTM C1314). Governs structural design per TMS 402.

“Design based on f'm = 2,000 psi per structural notes.” “Document f'm via unit-strength method; no prism tests required.” “Adjust grout or unit strengths if field tests do not support f'm.”


Thermal Bridging

Unintended heat flow through conductive elements (e.g., shelf angles, anchors) that reduces wall thermal performance. Mitigated by thermal breaks and detailing.

“Add thermal shims at shelf angles to reduce bridging.” “Detail veneer anchors with thermal isolation to limit heat loss.” “Model linear thermal transmittance (psi-value) in the energy analysis.”


Thin Veneer

A lightweight stone or brick cladding (typically 1/2–2 inches thick) adhered or mechanically fastened, offering reduced weight and different detailing than full-bed masonry.

“Install adhered manufactured stone with polymer-modified mortar.” “Use rainscreen mats behind thin brick over exterior sheathing.” “Provide movement joints per system manufacturer.”


TMS 402/602

The Masonry Society’s paired standards: TMS 402 (Building Code Requirements for Masonry Structures) and TMS 602 (Specification for Masonry Structures) governing design and construction.

“Comply with TMS 602 for workmanship, tolerances, and curing.” “Design walls per TMS 402 strength design provisions.” “Reference TMS details for control and expansion joints.”


U-Value (Thermal Transmittance)

A measure of heat flow through an assembly (lower is better). The reciprocal of R-value; used to demonstrate energy code compliance for walls.

“The wall assembly must achieve U-0.055 to meet energy code.” “Shelf angles increase U-value; add thermal breaks to compensate.” “Submit COMcheck showing wall U-values comply.”


Value Engineering

A systematic process to reduce cost while maintaining required performance and quality. Requires evaluating trade-offs and verifying code/spec compliance.

“VE: switch to CMU backup from cold-formed studs to reduce cost.” “VE: use Type N mortar instead of S where structurally acceptable.” “VE: replace stainless brick ties with galvanized in non-corrosive zones.”


Vapor Retarder

A membrane or layer that slows water vapor diffusion through a wall. Placement depends on climate and assembly; improper use can trap moisture.

“Avoid placing an interior vapor retarder behind an impermeable exterior veneer in hot-humid climates.” “Use a smart vapor retarder for mixed climates.” “Coordinate vapor control with air barrier and insulation placement.”


Weep Hole

Openings at the bottom of cavities or above flashings that allow water to drain from the wall. Essential to a functioning rainscreen/veneer system.

“Provide weeps above lintels and shelf angles over the flashing.” “Use mesh or rope weeps; keep them free of mortar.” “Space weeps per spec to ensure drainage and ventilation.”


Wythe

A vertical layer of masonry one unit thick. Walls can have one or multiple wythes, which may be bonded or tied together.

“Single-wythe CMU wall with IWR.” “Brick veneer wythe tied to CMU backup.” “Historic two-wythe solid brick walls require different detailing.”


Was this page helpful? We'd love your feedback — please email us at feedback@dealstream.com.